Modules of discrete control and input

io44du

The modules are designed for discrete control of different loads and inquiries for status of discrete inputs through the interface RS485 or USB.

FUNCTIONAL CAPABILITIES:

  • 4 groups of contacts (relay) and 4 discreet inputs 
  • Maximum switching current is up to 5 A and voltage is up to 240 V
  • Galvanically decoupled RS485 and USB 2.0 interfaces
  • Can be used as USB to RS485 converter
  • Ability to connect a number of devices to one bus
  • Control via industry standard ModBus protocol
  • Asynchronous registration of input events
  • Relays can be flipped for a defined time interval by one command
  • Access trough the virtual COM-port when connected to the PC by USB
  • Galvanically decoupled inputs can be configured for dry contacts or as voltage inputs
  • Reliable and practical enclosure that can be installed on DIN-rail
  • Setting and test software for module is supplied

 

PARAMETERS OF CONTACT PAIRS:   

Number of contact pairs

4

Maximum switching voltage

240 V

Maximum switching current

5 А

Galvanic decoupling from other network nodes

>1000V

Mechanical reliability of contacts 

10 000 000 responses

Electrical strength of contacts  

10 000 responses

Versions of contact pairs  

closed/open


PARAMETERS OF DISCRETE INPUTS:

Number of inputs   

4

Versions of inputs    

 

    Commutation to ground:      

 

        Internal tightening resistors   

 2.2 kOm

        Voltage of internal source   

 +4 V

  

Galvanically independent inputs controlled by the voltage

 

       Voltage    

+5/+12/+24 V                   

Overvoltage protection   

<2Unom.

Galvanic decoupling from other network nodes

>1000 V


RS485 INTERFACE PARAMETERS:

Supported speeds, baud    

4800, 9600, 14400, 57600,

19200, 38400, 115200

Parity check modes   

EVEN, ODD, NO

Galvanic decoupling from other network nodes     

1000 V

Electrostatic discharge protection                                              

20 kV

                
INTERFACE PARAMETERS USB*:

Specification   

2.0 

Electrostatic discharge protection                                              

20 kV 

Galvanic decoupling from other nodes in a circuit     

>1000V                           

*Only for IO44DU module


POWER PARAMETERS:   

Supply voltage   

10…30 V                            

Maximum consumption current  

150 mA

Power polarity changing protection                                              

implemented

 

Download short description (pdf, 440 kB) and full description (pdf, 790 kB).

 
© 2024 Video Internet Technologies Ltd.
All rights reserved.
I find: